Hot Products
Acrel AIM-D500-CA DC insulation monitor is a cutting-edge device designed for 0-1000V DC systems, ensuring power supply safety by continuously monitoring insulation resistance in IT systems.It meets the requirements of IEC 61557-8 and is compatible with the Combined Charging System (CCS) and CHAdeMO 3.0 standard.It can monitor the insulation resistance of DC charging stations with a nominal system voltage range from 50V up to 1000V.The device features a four-module enclosure and DIN-rail mounting, making it easy to install and integrate into existing systems.It also has the capability to measure system voltage and detect undervoltage and overvoltage conditions.Its stop mode allows users to disable the measuring pulse generator via the Modbus protocol, through the device menu, or by using an external button.The AIM-D500-CA is an ideal solution for applications such as power plants, substations, EV chargers, UPS systems, and solar systems.
Main Feature
l IEC61557-8
l Insulation Resistance Monitoring of DC Charging Station
l Rated Voltage: 50V~1000V
l Accordance with the CHAdeMO 3.0 & Combined Charging System (CCS)
l Undervoltage and Overvoltage Detection
l Stop Mode for Disabling the Measuring Pulse Generator
Dimension

Parameter
| Item | Parameter | |
| Supply voltage | Supply voltage Us | AC/DC 85~265V |
| Frequency | 50/60Hz | |
| Power consumption | ≤ 5 W | |
| IT system being monitored | Nominal system voltage with ACPD300, Un | DC 50…1000V |
| Nominal system voltage without ACPD300, Un | DC 50…400V | |
| Response values | Response value (Insulation prewarning) | Insulation alarm limit value…2MΩ |
| Response value (Insulation alarm) | 1kΩ…2MΩ | |
| Relative uncertainty | ±15%,±2kΩ | |
| Undervoltage detection | (80%~100%) Un(off)* | |
| Overvoltage detection | (100%~120%) Un(off)* | |
| accuracy | 1%,±1V | |
| CCS and CHAdeMO 3.0 mode | Permissible system leakage capacitance | ≤20μF |
| Measuring and display range of insulation resistance | 1kΩ…2MΩ | |
| Measurement uncertainty / Relative uncertainty | Ce≤5μF: ±15%,±2 kΩ | |
| Ce>5μF and RF>100 kΩ: ±15% | ||
| Response time | ≤10s | |
| Interface | RS485/Modbus-RTU | |
| Relay output | 2 x 1 n/o contact, AC 250V,3A, DC 30V,5A | |
| Environment | Operating temperature | -10℃ ~ +55℃ |
| Storage temperature | -20℃ ~ +70℃ | |
| Humidity | ≤95%RH, no condensation and corrosive gas | |
| Altitude | ≤2000m | |
| weight | AIM-D500-CA | 244.3g |
| ACPD300 | 86.1g | |
| Certification | CE, IEC,RoHS | |
Wiring

Network

Application
Hot Products

Optional 4DI2DO,12 channels temp measure,4 channels Residual current monitoring

2 × 4–20 mA DC measurement channels and 3 temperature measurement channels

Conduct centralized monitoring and management.

6 channel 3 phase or 18 channel 1 phase

With Different Size of CTs,easy to install D10,D16,D24,D36

Optional 4DI2DO,12 channels temp measure,4 channels Residual current monitoring

2 × 4–20 mA DC measurement channels and 3 temperature measurement channels

Conduct centralized monitoring and management.

6 channel 3 phase or 18 channel 1 phase

With Different Size of CTs,easy to install D10,D16,D24,D36

Optional 4DI2DO,12 channels temp measure,4 channels Residual current monitoring

2 × 4–20 mA DC measurement channels and 3 temperature measurement channels

Conduct centralized monitoring and management.
Inquiry