Hot Products
The AMC300L AC multi-loop intelligent power collection and monitoring device is mainly used for full electrical parameter measurement of multiple loops and can be connected to up to 6 three-phase loops or 18 single-phase loops with current input at the same time. It can measure voltage and current, power, power factor and other parameters.
Main Feature
● Channel: 6 channel 3 phase or 18 channel 1 phase :
● Rated Voltage: AC 3×220V/380V
● Accurancy: Voltage and current level 0.5, active energy level 1
● RS485(MODBUS-RTU)
● Opening size: 88*88mm
Dimension

Parameter
|
Technical Parameter |
Indicators |
|||
|
Input |
Frequency |
45~65Hz; |
||
|
Voltage |
Rated value: AC 3×220V/380V; |
|||
|
Overload: 1.2 times the rated value (continuous); 2 times the rated value/1 second; |
||||
|
Power consumption: ≤ 0.5VA (per circuit); |
||||
|
Current |
Rated value: AC 100A; |
|||
|
Overload: 1.2 times the rated value (continuous); 10 times rated value/1 second; |
||||
|
Power consumption: ≤ 0.5VA (per circuit); |
||||
|
Function |
Reserved pulse output |
Output mode: optocoupler pulse with Open collector; |
||
|
Communication |
Modbus RTU protocol ; Baud 1200~38400 |
|||
|
Switch-ing |
input |
4 dry contact inputs, 2 active (AC 220V input) |
||
|
output |
Output method: relay normally open contact output; Contact capacity: AC 250V/3A DC 30V/3A; |
|||
|
Temperature |
Temperature: -20-100 ℃ (accuracy ± 2 ℃) |
|||
|
Measurement accuracy |
Frequency 0.05Hz, voltage and current level 0.5, active energy level 1 |
|||
|
Auxiliary power supply |
AC/DC 85 to 265V; power consumption ≤ 10VA; |
|||
|
Security
|
power-frequency withstand voltage |
>AC 2kV/1min; |
||
|
insulation resistance |
Input and output terminals to casing>100M Ω; |
|||
|
Environment |
Working temperature:-20℃~+60℃; Storage temperature:-40℃~+70℃; Relative humidity:≤ 95% without condensation; Altitude: ≤ 2500m; |
|||
|
Electromagnetic compatibility |
Surge (impact) immunity test level 4; |
|||
|
Electrostatic discharge immunity test level 3 |
||||
|
Electrical fast transient pulse group immunity test level 3 |
||||
Wiring

Network
Application

Hot Products

Optional 4DI2DO,12 channels temp measure,4 channels Residual current monitoring

2 × 4–20 mA DC measurement channels and 3 temperature measurement channels

Conduct centralized monitoring and management.

6 channel 3 phase or 18 channel 1 phase

With Different Size of CTs,easy to install D10,D16,D24,D36

Optional 4DI2DO,12 channels temp measure,4 channels Residual current monitoring

2 × 4–20 mA DC measurement channels and 3 temperature measurement channels

Conduct centralized monitoring and management.

6 channel 3 phase or 18 channel 1 phase

With Different Size of CTs,easy to install D10,D16,D24,D36

Optional 4DI2DO,12 channels temp measure,4 channels Residual current monitoring

2 × 4–20 mA DC measurement channels and 3 temperature measurement channels